AP-219

Technical Information

Substrate Min. 64mm timber or steel stud wall with a minimum of one layer of 13mm (or greater) FR plasterboard on each side, with or without insulation.

Min. 90mm concrete wall

Service range DN90mm HDPE pipe
Annular gap 0.0-11.8mm
AGNI-Product AGNI-Collar, AGNI-Seal
Protection installation From both sides of the wall

 

Compliance Information

Standards AS1530.4-2014, AS4072.1-2005
FRL/FRR -/60/60
Reference PF25036, PF25004

Documents

Download Installation InstructionsDownload RIRF25036