Technical Information |
|
| Substrate | Min. 64mm timber or steel stud wall with a minimum of two layers of 13mm (or greater) FR plasterboard on each side, with or without insulation.
Min. 116mm concrete wall |
| Service range | 32mm Copper Pipe with 32mm thick nitrile rubber insulation
+ 15mm Copper Pipe with 25mm thick nitrile rubber insulation |
| Annular gap | 7.2 – 14.2mm |
| AGNI-Product | AGNI-Black, AGNI-Sleeve |
| Protection installation | From both sides of the wall |
Compliance Information |
|
| Standards | AS1530.4-2014, AS4072.1-2005 |
| FRL/FRR | -/120/120 |
| Reference | PF25008 |