AP-236

Technical Information

Substrate Min. 64mm timber or steel stud wall with a minimum of two layers of 13mm (or greater) FR plasterboard on each side, with or without insulation.

Min. 116mm concrete wall

Service range DN65mm uPVC pipe with coupling
Annular gap 5.6mm
AGNI-Product AGNI-Collar, AGNI-Seal
Protection installation From both sides of the wall

 

Compliance Information

Standards AS1530.4-2014, AS4072.1-2005
FRL/FRR -/120/120
Reference FRT251395

Documents

Download Installation InstructionsDownload FRT251395

Products Used in This System

AGNI-Seal®

Learn More
agni-seal

AGNI-Collar

Learn More
Designed and developed by Maxim Seryakov
Agnitek PTY Limited © 2026 All Rights Reserved