AP-233

Technical Information

Substrate Min. 64mm timber or steel stud wall with a minimum of one layer of 13mm (or greater) FR plasterboard on each side, with or without insulation.

Min. 90mm concrete wall

Service range DN100mm Copper Pipe
Annular gap 0.8-6.1mm
AGNI-Product AGNI-Seal, AGNI-Shield, AGNI-Strap
Protection installation From both sides of the wall

 

Compliance Information

Standards AS1530.4-2014, AS4072.1-2005
FRL/FRR -/60/60
Reference PF25042

Documents

Download Installation InstructionsDownload RIRF25042