Technical Information

Substrate Min. 64mm timber or steel stud wall with a minimum of two layers of 13mm (or greater) FR plasterboard on each side, with or without insulation.

Min. 116mm concrete wall

Service range DN50mm copper pipe with  nitrile rubber insulation from 9mm up to 38mm thick
Annular gap DN50mm with 32mm insulation – 8.9 – 11.1mm
AGNI-Product AGNI-Black, AGNI-Sleeve
Protection installation From both sides of the wall

 

Compliance Information

Standards AS1530.4-2014, AS4072.1-2005
FRL/FRR -/120/120
Reference PF25008