Technical Information |
|
Substrate | Min. 64mm timber or steel stud wall with a minimum of two layers of 13mm (or greater) FR plasterboard on each side, with or without insulation.
Min. 116mm concrete wall |
Service range | DN50mm copper pipe with nitrile rubber insulation from 9mm up to 38mm thick |
Annular gap | DN50mm with 32mm insulation – 8.9 – 11.1mm |
AGNI-Product | AGNI-Black, AGNI-Sleeve |
Protection installation | From both sides of the wall |
Compliance Information |
|
Standards | AS1530.4-2014, AS4072.1-2005 |
FRL/FRR | -/120/120 |
Reference | PF25008 |