AE-131

Technical Information

Substrate Min. 64mm timber or steel stud wall with a minimum of one layer of 13mm (or greater) FR plasterboard on each side, with or without insulation.

Min. 90mm concrete wall

Service range 1 x PE pair coils + 1 x TPS cables
Annular gap 3.5 - 30mm
AGNI-Products AGNI-Wrap 50, AGNI-Black
Penetration side Both sides of the wall

Fire side only

Non-fire side only

Protection installation From both sides of the wall

 

Compliance Information

Standards AS1530.4-2014, AS4072.1-2005
FRR/FRL -/60/60
Reference PF24102