Technical Information |
|
| Substrate | Fire-rated plasterboard ceiling (min. one layer of 13mm plasterboard or greater) |
| Service range | 1-3 x Pair PE/FR + 1-3 x 25mm uPVC pipe + 1-3 x TPS cables |
| Annular gap | 3.5mm - 20mm |
| AGNI-Products | AGNI-Seal, AGNI-Wrap 50, AGNI-Clips, AGNI-Strap |
| Protection installation | Asymmetrical – installed on the fire side only |
Compliance Information |
|
| Standards | AS1530.4-2014, AS4072.1-2005 |
| FRR/FRL | -/30/30 in the ceiling with FRR 30/30/30
-/60/60 in the ceiling with FRR 60/60/60 |
| Reference | PF24079 |