Technical Information |
|
Substrate | Min. 64mm steel / timber stud wall with a minimum of two layers of 13mm (or greater) FR plasterboard on each side, with or without insulation.
Min. 116mm concrete wall/masonry wall/block wall |
AGNI-Box services | D1 cable configuration |
Annular gap | 0 - 5mm |
AGNI-Products | AGNI-Box, AGNI-Seal |
Protection installation | Both sides of the wall |
Compliance Information |
|
Standards | AS1530.4-2014, AS4072.1-2005 |
AGNI-Box system FRL/FRR | -/120/90 |
AGNI-Box services FRL/FRR | 1 x XLPE single core cable -/120/90
1 x APEC 2023 X-90 Electra Cable -/120/90 3 x Electra 2018 V-90 Electric Cable -/120/120 8 x Electra Cable 2023 X-90 -/120/90 |
Reference | PF24110 |