Technical Information |
|
Substrate | Min. 64mm steel / timber stud wall with a minimum of two layers of 13mm (or greater) FR plasterboard on each side, with or without insulation.
Min. 116mm concrete wall/masonry wall/block wall |
AGNI-Box services | DN40mm steel pipe
DN 60mm steel pipe DN25mm copper pipe DN50mm copper pipe |
Annular gap | 0 - 5mm |
AGNI-Products | AGNI-Box, AGNI-Seal |
Protection installation | Both sides of the wall |
Compliance Information |
|
Standards | AS1530.4-2014, AS4072.1-2005 |
AGNI-Box system FRL/FRR | -/120/30 |
AGNI-Box services FRL/FRR | DN40mm steel pipe -/120/90
DN60mm steel pipe -/120/60 DN25mm copper pipe -/120/60 DN50mm copper pipe -/120/30 |
Reference | PF24110 |